Alpha FXM 650, 1100, 2000 Power Modules
- 650 W/VA, 1100 W/VA and 2000 W/VA uninterruptible power supply modules for a
variety of power requirements and applications.
- Ruggedized design offers a wide operating temperature range of -40°C to 74°C
(-40°F to 165°F) for the most extreme operating environments.
- Independently programmable dry contact relays allow tracking and controlling of key
functions.
- External communications via RS-232 port or optional Ethernet SNMP communication
interface provides local or remote monitoring and control.
- Wide Automatic Voltage Regulation range allows continuous operation without
transferring to backup mode during voltage surge or sag.
The Alpha FXM uninterruptible power supply (UPS) modules provide clean, reliable power control and
management as part of a complete UPS solution. Each model is available in either North American (120V) or
International (230V) variants, both with auto-frequency (60Hz/50Hz). Automatic Voltage Regulation (AVR) provides
power stability in unpredictable environments and constant voltage during variable power conditions. Temperature
compensated battery charging protects batteries from over charging at extreme temperatures, extending battery life.
Event and alarm logging with time and date stamping simplifies and accelerates troubleshooting. Control and power
connection panels can be rotated for mounting and display in any orientation for viewing convenience.
Nominal Specifications| Power Module | FXM 650 | | FXM 1100 | | FXM 2000> |
|---|
| North America | International | North America | International | North America | International |
|---|
| Battery String Voltage: | 24Vdc/48Vdc | 24Vdc | 48Vdc | 48Vdc | 48Vdc | 48Vdc |
|---|
| Nominal Voltage: | 120Vac | 230Vac | 120Vac | 230Vac | 120Vac | 230Vac |
|---|
| Nominal Frequency: | 60Hz | 50Hz> |
|---|
| Input Current: | 8A | 4.5A | 16A | 8.0A | 20A | 12A |
|---|
| Input Voltage Range: | 85-175Vac | 150-328Vac | 85-175Vac | 150-328Vac | 85-150Vac | 150-281Vac |
|---|
| Output Current: | 5.4A | 2.8A | 9.1A | 4.78A | 16.6A | 8.69A |
|---|
| Output Voltage Regulation: | +/- 10% over input voltage range> |
|---|
| Output power at 50°C: | 650W/VA | 650W/VA | 1100W/VA | 1100W/VA | 2000W/VA | 2000W/VA |
|---|
General Specifications| Input voltage range |
|---|
| 120VAC: | 85 to 175VAC* (to 150VAC for FXM 2000) |
|---|
| 230VAC: | 150 to 328VAC* |
|---|
| Output voltage range |
|---|
| Regulation: | ±10% over full input voltage range |
|---|
| Waveform: | Pure sine wave |
|---|
| Typical efficiency (full resistive load): | >98% |
|---|
| Typical output voltage THD: | <3% |
|---|
| Typical transfer time: | <5ms |
|---|
| Audible noise @ 1m: | 45dBA |
|---|
| *Without transferring to backup mode |
|---|
Mechanical Specifications| Power Module: | FXM 650 | FXM 1100 | FXM 2000 |
|---|
| Dimensions WxHxD: | 432x88x229mm / 7”x3.47”x9” / | 394x133x222mm / 15.5”x5.22”x8.75” / | 394x133x222mm / 15.5”x5.22”x8.75” |
|---|
| Weight ( kg/lb): | 11/25 | 16/35 | 16/35 |
|---|
Environmental Specifications| Operating temperature: | -40º to 74ºC (-40º to 165ºF) |
|---|
| Storage temperature: | -40º to 75ºC (-40º to 168ºF) |
|---|
| Operating altitude: | 3658m/12,000ft |
|---|
| Operating humidity: | Up to 95% |
|---|
Agency Compliance| Electrical safety North America | UL1778, CSA 22.2 No 107.3-03 |
|---|
| Electrical safety International | CE EN62040-1-2 |
|---|
| Marks | CCSAUS /CE |
|---|
| EMI Compliance | FCC/IC/CE Class A/CISPR 22 / EN 50022/EN 62040-2 (230VAC version only) |
|---|
Standard Features| Automatic Voltage Regulation (AVR), Automatic frequency sensing (60Hz/50Hz), Standard RS-232 serial port (optional internal Ethernet SNMP), Novus User Software: A user friendly Windows™ based GUI, Emergency Power Off (EPO) input, Variable speed fan with fan failure alarm, Circuit breaker protection on the input and external battery input, Three mounting configurations: wall, shelf or rack (rack mount kit required), Generator-ready for extended runtime option, Three user inputs: self test, alarm, shutdown, User adjustable charger (off, 3A, 6A, 10A), 100 historical events logged with time |
Options| Ethernet SNMP communication interface, Rackmount kit |
| Title |
Type |
Version |
Date |
|
Alpha FXM 650
|
Datasheet
|
048-0012-00 Rev. B
|
January 7, 2011
|
|
Alpha FXM 1100
|
Datasheet
|
048-0013-00 Rev. B
|
January 7, 2011
|
|
Alpha FXM 2000
|
Datasheet
|
048-0014-00 Rev. B
|
January 7, 2011
|
|
Novus User Software for Firmware 1.06_Eng
|
Software
|
2.01
|
June 12, 2008
|
|
FXM Communication Module Data Sheet - English (LTR)
|
Datasheet
|
049-084-41-001
|
April 1, 2006
|
|
FXM Communications Module Operating Manual (LTR)
|
Manual
|
017-201-B0
|
September 6, 2006
|
|
Novus FXM 1100 Manual and Firmware
|
Software
|
1.06
|
June 12, 2008
|
|
Novus FXM 2000 Manual and Firmware
|
Software
|
1.06
|
June 12, 2008
|
|
Novus FXM 650 Manual and Firmware
|
Software
|
1.06
|
June 12, 2008
|
|
FXM Communication Module Data Sheet - English (A4)
|
Datasheet
|
049-084-45-001
|
April 1, 2006
|
|
Novus FXM Operator's Manual - firmware 1.06
|
Manual
|
017-201-B0
|
April 1, 2008
|
|
Novus FXM Operator's Manual previous to firmware 1.06
|
Manual
|
017-201-B0
|
September 1, 2006
|