Alpha Technologies Inc.
Phone: 360 647 2360
Email: alpha@alpha.com
Tempest Te30
Tempest Te30
  • Modular enclosure design for mid size applications
  • Provides multiple enclosure line-ups including power, battery and radio equipment installations
  • Air conditioning, fan cooling and vented options available
  • Nema 3R rating (IP55)
  • Multiple cable access points


The mid-size Te30 enclosure line-up provides up to 27ru of equipment in a 23" rack. A variety of HVAC options maintain a clean internal temperature controlled enviroment for reliable equipment operation in all kinds of outdoor environmental conditions. The Te30 is designed for installation flexibility. A number of cable entry locations are provided along with a cable management plinth option. Cable entry panels provide access by conduit, multiple cable entry assemblies and water tight fittings. In addition, the Te30 provides options for various AC service entrance and distribution panels adding installation and application flexibility. The Te30 provides an excellent solution for general purpose mid-size enclosure applications.
Tempest Te30
Electrical Specifications
Input voltage120/240VAC 100A 1 Ø
Generator switch/ Generator connectorOptional
TVSSOptional
AC panels/breakersConfigurable - contact factory
Mechanical Specifications
Part number029-016-20
Dimensions
mm1483H x 762W x 762D, including 254mm plinth
inches58.4H x 30W x 30D, including 10” plinth
WeightApprox. 227 kg (500lb) no batteries, no rectifiers
MountingPad or platform
EnclosureAluminum shell 5052-H32
Internal rack23”, 26RU
Environmental Specifications
Operating temperature-40 to +46°C (-40 to +115°F)
Storage temperature-40 to +85°C (-40 to +185°F)
Humidity0 to 95% non-condensing
Elevation3600m, see operating temperature (12,000ft)
Weather tightnessNEMA Type 3R
Audible noise44dBA @ 7 metres (23ft) (air conditioned system)
Other Information
Alarm
ConnectionTerminal block
DescriptionHigh/low temp & intrusion
Chassis groundMultiple connection
SecurityPad lockable doors
Standards
Enclosure ratingsCSA/UL type 3R
IP55 equivalent
Product safetyCSA/UL 60950
SeismicDesigned to meet zone 4 requirements
Related Components
Cooling options5000 BTU/hr. air conditioner on front door
DC fan cooling (and/or backup)
Vented
HeatingUp to 550W, 100-120VAC 50/60Hz
Document Downloads
Title Type Version Date
Tempest Te30 Datasheet_English Datasheet June 1, 2008