- 4.0HP offering 240 cable runtime minutes
- 3.5HP offering 210 cable runtime minutes
- Provides up to 20% increased runtime in coldest climates
- Pure lead technology provides up to 10% increased life expectancy
- Increased shelf life from 6 to 18 months at 25°C
- 4-5 year full warranty (varies by location)
String Count Reduction to Reduce OpEx - You can use fewer AlphaCell HP batteries compared to
standard batteries, while maintaining network runtime reliability. For power supply loads that are less than 8 Amps you can achieve a 4 hour runtime using a single string of 4.0HP batteries compared to using two strings of competitive batteries. Consult your Alpha sales engineer for a free network analysis on how to potentially reduce your OpEx by up to 25 percent while increasing the reliability of the batteries in your network.
Specifications| Models: | 3.5HP | 4.0HP |
|---|
| Warranty: | 4-5 year full replacement | 4-5 year full replacement |
|---|
| Service Life: | Extended | Extended |
|---|
| Typical Runtime (minutes): | 210 | 240 |
|---|
| Sealed VRLA: | Valve regulated lead acid | Valve regulated lead acid |
|---|
| Heat Resistant: | Extreme | Extreme |
|---|
| Hydrogen Emission: | Low | Low |
|---|
| Terminals: | Threaded insert 1/4" - 20 UNC | Threaded insert 1/4" - 20 UNC |
|---|
| Electrical |
|---|
| Cell Per Unit: | 6 | 6 |
|---|
| Voltage Per Unit: | 12.8 | 12.8 |
|---|
| Conductance Value: | 1700 | 2100 |
|---|
| Max. Discharge Current (A): | 800 | 900 |
|---|
| Short Circuit Current (A): | 2800 | 3200 |
|---|
| 10 Second Volts @ 100A: | 11.7 | 11.8 |
|---|
| Ohms Impedance 60Hz: | 2.7 | 2.2 |
|---|
| BCI Group Size: | 31 | 31 |
|---|
| Mechanical |
|---|
| Dimensions H x W3 x D3 (in/mm): | 8.5 x 13.4 x 6.8 / 223.5 x 337.8 x 172.7 | 8.5 x 13.4 x 6.8 / 223.5 x 337.8 x 172.7 |
|---|
| Weight (lb/kg): | 68 / 30.8 | 74 / 35.6 |
|---|
| Operating Temperature Range |
|---|
| Discharge: | -40 to 60°C / -40 to 140°F | -40 to 60°C / -40 to 140°F |
|---|
| Charge (with Temp compensation): | -40 to 60°C / -40 to 140°F | -40 to 60°C / -40 to 140°F |
|---|
| Float Charging Voltage (Vdc): | 13.5 to 13.8 | 13.5 to 13.8 |
|---|
| AC Ripple Charge: | 0.5% RMS or 1.5% of float charge voltage recommended for best results. Max. allowed = 4%V pk to pk | 0.5% RMS or 1.5% of float charge voltage recommended for best results. Max. allowed = 4%V pk to pk |
|---|