AlphaCell HPL-FT
Front terminal design with protective covers
Specifically designed for mission-critical applications
High cyclic life capability
Flame retardant case and cover (to UL94VO)
3-step terminal seal design ensures leak-free operation
Integral handles (115HPL-FT, 220HPL-FT) for ease of handling
Approved as non-hazardous cargo for ground/sea/air transportation
Ideally suited for use in Alpha NPS and FT enclosures
Alpha expands its AlphaCell battery family to include the HPL-FT Series of front terminal batteries for Broadband Cable and Telecommunication applications. The AlphaCell HPL-FT series are valve regulated lead acid batteries designed for long life. Benefits of these new batteries include: central gassing system, snap-in front covers, integral flame arrestor, construction from recyclable materials and low self discharge rates. The HPL-FT 115 and 220 series batteries feature a handle for carrying convenience.
AlphaCell HPL-FT Batteries
General Specifications
70HPL-FT
115HPL-FT
220HPL-FT
Standard Warranty1:
3 years
3 years
3 years
Service Life:
Long
Long
Long
VRLA Battery Type:
High performance Lead Alloy
High performance Lead Alloy
High performance Lead Alloy
Heat Resistant:
High
High
High
Hydrogen Emission:
Low
Low
Low
Terminals:
14mm Insert M8 x 1.25 thread
14mm Insert M8 x 1.25 thread
14mm Insert M8 x 1.25 thread
Terminal Torque:
8Nm
8Nm
8Nm
Case Material:
VO
VO
VO
Typical Runtime (min):
70
115
220
Cells Per Unit:
6
6
6
Voltage Per Unit:
12.8
12.8
12.8
Conductance Value:
1050
1200
1600
Max. Discharge Current (A):
1000
1000
1000
Short Circuit Current (A):
1400
2000
3500
10 Second Volts @ 100A:
11.3
11.5
11.7
Ohms Impedance 1 kHz:
6.5mOhms
4.1mOhms
2.5mOhms
Capacity at 20hrs (to 1.75VPC) @ 25°C/77°F:
42Ah
62Ah
107Ah
Weight (lb/kg):
27.9/15.3
46.2/22.2
78.5/36
Height (in/mm):
8.21/209
10.3/263
11.3/287
Width (in/mm):
3.81/97
4.2/103
4.24/108
Depth (in/mm):
9.84/250
11.3/287
15.59/396
Operating Temperature Range
Discharge (C):
-40°C to 60°C (-40°F to 140°F)
-40°C to 60°C (-40°F to 140°F)
-40°C to 60°C (-40°F to 140°F)
Charge (with temp compensation)(C):
-40°C to 60°C (-40°F to 140°F)
-40°C to 60°C (-40°F to 140°F)
-40°C to 60°C (-40°F to 140°F)
Float Charging Voltage @ 25°C/77°F (Vdc):
13.5 to 13.6
13.5 to 13.6
13.5 to 13.6
AC Ripple Charger:
0.5% RMS or 1.5% of float charge voltage recommended for best results. Max. allowed = 4% P-P>
Document Downloads
Title
Type
Version
Date
AlphaCell HPL-FT Batteries Datasheet_Eng
Datasheet
049-294-10-A001
December 8, 2009