Alpha Technologies Inc.
Phone: 360 647 2360
Email: alpha@alpha.com
Fiber Backhaul
AlphaCell HPL-FT
  • Front terminal design with protective covers
  • Specifically designed for mission-critical applications
  • High cyclic life capability
  • Flame retardant case and cover (to UL94VO)
  • 3-step terminal seal design ensures leak-free operation
  • Integral handles (115HPL-FT, 220HPL-FT) for ease of handling
  • Approved as non-hazardous cargo for ground/sea/air transportation
  • Ideally suited for use in Alpha NPS and FT enclosures


Alpha expands its AlphaCell battery family to include the HPL-FT Series of front terminal batteries for Broadband Cable and Telecommunication applications. The AlphaCell HPL-FT series are valve regulated lead acid batteries designed for long life. Benefits of these new batteries include: central gassing system, snap-in front covers, integral flame arrestor, construction from recyclable materials and low self discharge rates. The HPL-FT 115 and 220 series batteries feature a handle for carrying convenience.
AlphaCell HPL-FT Batteries
General Specifications
70HPL-FT115HPL-FT220HPL-FT
Standard Warranty1:3 years3 years3 years
Service Life:LongLongLong
VRLA Battery Type:High performance Lead AlloyHigh performance Lead AlloyHigh performance Lead Alloy
Heat Resistant:HighHighHigh
Hydrogen Emission:LowLowLow
Terminals:14mm Insert M8 x 1.25 thread14mm Insert M8 x 1.25 thread14mm Insert M8 x 1.25 thread
Terminal Torque:8Nm8Nm8Nm
Case Material:VOVOVO
Typical Runtime (min):70115220
Cells Per Unit:666
Voltage Per Unit:12.812.812.8
Conductance Value:105012001600
Max. Discharge Current (A):100010001000
Short Circuit Current (A):140020003500
10 Second Volts @ 100A:11.311.511.7
Ohms Impedance 1 kHz:6.5mOhms4.1mOhms2.5mOhms
Capacity at 20hrs (to 1.75VPC) @ 25°C/77°F:42Ah62Ah107Ah
Weight (lb/kg):27.9/15.346.2/22.278.5/36
Height (in/mm):8.21/20910.3/26311.3/287
Width (in/mm):3.81/974.2/1034.24/108
Depth (in/mm):9.84/25011.3/28715.59/396
Operating Temperature Range
Discharge (C):-40°C to 60°C (-40°F to 140°F)-40°C to 60°C (-40°F to 140°F)-40°C to 60°C (-40°F to 140°F)
Charge (with temp compensation)(C):-40°C to 60°C (-40°F to 140°F)-40°C to 60°C (-40°F to 140°F)-40°C to 60°C (-40°F to 140°F)
Float Charging Voltage @ 25°C/77°F (Vdc):13.5 to 13.613.5 to 13.613.5 to 13.6
AC Ripple Charger:0.5% RMS or 1.5% of float charge voltage recommended for best results. Max. allowed = 4% P-P
Document Downloads
Title Type Version Date
AlphaCell HPL-FT Batteries Datasheet_Eng Datasheet 049-294-10-A001 December 8, 2009