Alpha Technologies Inc.
Phone: 360 647 2360
Email: alpha@alpha.com
Wireless Transport Enclosure (WTE)
Wireless Transport Enclosure (WTE)
  • Equipment mounting area is 17 RU
  • Equipment rails are front-to-back adjustable, suitable for mounting 19 inch rack mount equipment
  • Integrates Heat Exchanger and Thermoelectric Colling System
  • Equipment area is cooled by an Air-to-Air heat exchanger with variable speed blower control.
  • Internal L14-30P Generator inlet plug with generator cord access through door.
  • Optional precast mounting pad


The Wireless Transport Enclosure (WTE) is ideal for Wireless Backhaul Business Service applications. It offers a self-contained total power solution for a wide range of applications including wireless outdoor base stations, wireless IP access and bulk power. With a compact 24” x 24” footprint, the WTE features a standard 19” rack mount system with has 17RU (front/rear) of rack space, and an internal Breaker Distribution Panel with GFCI and Surge Protection.

Its two compartments share a common door keeping batteries and electronics isolated in operation, but quickly and easily accessible for set-up, maintenance or repairs. Thermal management is provided by a door-mounted 48Vdc heat exchanger for the equipment area and a 48Vdc Thermoelectric cooling/heating unit for the battery area. The available 6” Plinth system is well-suited for staged installations and an internal L14-30P generator inlet plug enables connection with a portable generator for backup powering capability.
Wireless Transport Enclosure (WTE)
Enclosure Specifications
Mechanical
Outer Dimensions HxWxD (in/mm):70 x 24 x 29 (1778 x 610 x 737)
Weight (lb/kg):330 / 150
Equipment Space:Adjustable 19" 17RU plus 2 battery trays
Access:Front hinged door and rear list off door
Door Latch/Hinge Type:1/4 turn padlockable / reversible 4 position lift off hinge
Material:High Strength Corrosion Resistant Aluminum
Finish:Almond Color Powdercoat Finish
CSA/UL:60950-22 ITE electrical enclosure
NEMA Rating:Type 3R
Battery Storage AreaTwo shelves
Optional 6" Plinth
Alpha P/N746-080-20
Dimensions (in/mm):6H x 24W x 24D (152 x 610 x 610)
System Specifications
• Dual compartments
- Upper compartment - heat exchanger
- Lower compartment - thermoelectric cooling
• Two battery trays (Consult factory for battery specifications)
• Front to back adjustable 19" equipment mounting rails
• Internal AC panel
• Generator plug and transfer switch
• Alarm terminal block
• Ground bar
System Options
Optional pre-formed mounting pad
Consult factory for custom system solutions
Accessories
DescriptionPart Number
Precast Polymer Concrete PadP/N 641-131-10
Pour-in-place Pad DrawingTBD
Field Installed Right to Left door mounting kitP/N 746-079-20
Concrete-to-Aluminum Corrosion Barrier MSTCD, 3/6" RBR, WTEP/N 648-173-10
Kit. Plinth, 6"T, WTE, 24" x 24"P/N 746-080-20
Touch-up Spray Paint, AlmondP/N 972-056-10
Pad Mounting Hardware Kit (4 Hilti KBII sleeve anchors 1/2 x 3-3/4); for pour-in-place padsP/N 745-592-21
Pad Mounting Hardware (4 Hilti HSLG M12/0 *60 heavy duty sleeve anchors) requires 12mm metric drill Kit for Zone 4; for pour-in-place padsP/N 745-592-20
Document Downloads
Title Type Version Date
Wireless Transport Enclosure (WTE) Datasheet_Eng Datasheet 049-332-10-A001 October 26, 2009
Wireless Transport Enclosure (WTE) Technical Manual Manual 021-517-B0-001 Rev. A December 14, 2009