Select Your Country
Lectro ZTT Plus Series
  • Zero Transfer Time to standby means your network is unaffected by utility outages
  • Digital LCD Panel provides true RMS readings without using separate hand-held meters
  • Modular construction for inverter hot-swap capability without shutting down the network


The ZTT/Plus employs a hot swappable inverter module in a rugged enclosure for easy field maintenance without interrupting network operations. Standard features include LCD panel, a front access DIN port for connection to various third party transponders, and a robust ferro capable of handling 200% short duration overloads. Following an outage, the ZTT/Plus delivers a constant 6A charging current under all load and line conditions. In the event of a short, the output is protected by a software controlled circuit breaker that cycles to protect downstream network amplifiers.
General Specifications
Battery Charging
Temperature Compensation±2.8mV/Cell/°C
Constant Current Operation2.41V/Cell to 90% capacity
Constant Voltage Operation2.30V/Cell
Environmental
Operating Range-40° to 55°C / -40 to 131°F
Humidity5 to 95% non-condensing
Mechanical
Dimensions (in/mm)7 x 16.5 x 13 / 178 x 419 x 330
Weight (lb/kg)65/29
FinishBlack Epoxy Powdercoat
Model ZTT/Plus (120V)
Specifications
ELectrical
Input Voltage Range (Vac)120V
Input Voltage Regulation-20 to 10%
Nominal Input Current
@ 87Vrms13.4A
@ 60Vrms9.6A
Input Frequency60Hz ±3Hz
DC Voltage36Vdc
Low DC Voltage Cutout1.75V/Cell
Output Voltage Field Selectable (Vac)60/75/87V
Output Regulation±3%
Rated Output Current Inverter15A rms
Output Frequency60Hz ±1
WaveformQuasi Square wave
Slew Rate<100V/ms
Crest Ratio (Peak RMS)1.31
Efficiency
@ 87Vrms89.9%
@ 60Vrms86.9%
Agency Compliance
Safety RegulationUL 1778, CSA C22.2 No.107.1-M95, FCC Part 15 Class A
Overload Protection
Foldback (Typical @ Nominal Input)
87V Tap200%
60V Tap300%
Output Current Into Short
87V Tap20A rms
60V Tap28A rms
Output Current Into Short Inverter OperationInverter shutdown upon long duration short with auto retry upon cool down period (approximate 5sec)
Model ZTT/Plus (220V)
Specifications
ELectrical
Input Voltage Range (Vac)220V
Input Voltage Regulation-20 to 10%
Nominal Input Current
@ 87Vrms7.4A
@ 60Vrms5.3A
Input Frequency60Hz ±3Hz
DC Voltage36Vdc
Low DC Voltage Cutout1.75V/Cell
Output Voltage Field Selectable (Vac)60/87V
Output Regulation±3%
Rated Output Current Inverter15A rms
Output Frequency60Hz ±1
WaveformQuasi Square wave
Slew Rate<100V/ms
Crest Ratio (Peak RMS)1.31
Efficiency
@ 87Vrms88.9%
@ 60Vrms85.3%
Agency Compliance
Safety RegulationUL 1778, CSA C22.2 No.107.1-M95, FCC Part 15 Class A
Overload Protection
Foldback (Typical @ Nominal Input)
87V Tap200%
60V Tap300%
Output Current Into Short
87V Tap22A rms
60V Tap32A rms
Output Current Into Short Inverter OperationInverter shutdown upon long duration short with auto retry upon cool down period (approximate 5sec)
Document Downloads
Title Type Version Date
Lectro ZTT/Plus Manual Users Guide Manual 164201085 Rev. F0 June 1, 2006
Lectro ZTT+ Data Sheet - English (A4) Datasheet 049-221-18-002 January 1, 2006
Lectro ZTT+ Data Sheet - English (LTR) Datasheet 049-221-17-002 January 1, 2006