  • Clean, uninterruptible backup power ensures your system will remain up and running during power outages.
  • Wide range Automatic Voltage Regulation without going to batteries extends battery life, even during periods of surge or sag in voltage from utility power.
  • External communications via RS-232 port or (optional) Ethernet SNMP interface provides local or remote monitoring control.
  • Independently programmable control and report relays allow tracking and controlling of key functions.
  • User-friendly LCD display allows "at-a-glance" monitoring and troubleshooting.
  • Event and alarm logging with time and date stamping simplifies and accelerates troubleshooting.
  • A wide operating temperature range of -40º to 74ºC (-40º to 165ºF) is suitable for most extreme operating environments.
  • Temperature compensated battery charging protects batteries from over charging at extreme temperatures.


The Novus Micro Series provides constant, reliable backup power for Access Control, Security Public Utility and Telecommunications applications in a compact all-in-one enclosure. The Novus Micro UPS Series provides the same functionality as the Novus FXM Series, for lower power applications in a single, easy to install cabinet. Optional add-on battery cabinets support applications where longer backup times are required. Each power level is available in either North American (120VAC/60Hz) or International (230VAC/50Hz) variants.
Novus Micro Series
Agency Compliance
Electrical safety:UL1778, CSA 22.2 No. 107.3, EN50091-1-2, EN60950
EMI:Level A FCC, CISPR22, EN55022
Marks:CCSAUS , CE
Standard Features
Hot-swappable batteries
Novus User Software: Windows™-based communication software
External user input: self test, alarm and EPO (Micro 1000)
Wall, pole, or pedestal mountable (XL and XL2)
Automatic Voltage Regulation (AVR)
User adjustable charger (3A, 6A, 10A)
Programmable dry contact relays (NC & NO)
Reverse battery polarity protection
Nominal Specifications
Power ModuleNovus Micro 300Novus Micro 1000
Nominal Voltage120Vac / 230Vac120Vac / 230Vac
Nominal Frequency60Hz / 50Hz60Hz / 50Hz
Input Current5.4A / 2.8A14A / 7.3A
Output Current2.5A / 1.3A8.3A / 4.3A
Output Power at 50°C300W/VA / 300W/VA1000W/VA / 1000W/VA
Programmable Relays2 / 21 / 1
Battery String Voltage24Vdc / 24Vdc48Vdc / 48Vdc
General Specifications - Performance
Input Voltage Range (120VAC)85 to 175Vac w/o going to batteries
Input Voltage Range (230VAC)150 to 328Vac w/o going to batteries
Output Voltage Regulation±10% over full input voltage range
Output Voltage WaveformPure sine wave
Typical Efficiency (full resistive load)>98%
Typical Output Voltage THD<3%
Typical Transfer time<5ms
Audible noise @ 1m45dBA
Mechanical Specifications
Novus MicroMicroMicro XLMicro XL3
Width (in/mm)14.1 / 35814.1 / 35814.1 / 358
Height (in/mm)19.67 / 499.630.57 / 776.552.37 / 1330.2
Depth (in/mm)11.56 / 293.611.56 / 293.611.56 / 293.6
Unit Weight (lb/kg)
Micro 30044/2050/2370/32
Novus Micro 100047/2152/2462/28
Environmental Specifications
Operating Temperature-40 to 74°C (-40 to 165°F)
Storage Temperature-40 to 75°C (-40 to 168°F)
Operating Altitude (ft/mm)12,000/3658
Operating HumidityUp to 95%
Battery Runtimes
Novus MicroNovus Micro XLNovus Micro XL3
2x50Ah Batteries2x109Ah Batteries4x109Ah Batteries
300W2hrs 12mins5hrs 22mins11hrs 45mins
4x18Ah Batteries4x50Ah Batteries4x109Ah Batteries
1000W26mins1hr 27mins3hrs 36mins
Document Downloads
Title Type Version Date
Novus Micro Series Datasheet - English Datasheet 048-084-42-002 August 8, 2007
Novus Micro Datasheet_Spanish (LTR) Datasheet 049-084-33-002 July 1, 2007
Novus Micro Operating Manual - English (LTR) Manual 017-221-B0 April 1, 2008
Novus User Software for Firmware 1.06_Eng Software 2.01 June 12, 2008
Novus Micro 1000 Manual and Firmware Software 1.06 June 12, 2008
Novus Micro 300 Manual and Firmware Software 1.06 June 12, 2008