Alpha Technologies Inc.
Phone: 360 647 2360
Email: alpha@alpha.com
Cordex 1kW Modular Switched Mode Rectifier
Cordex 1kW Modular Switched Mode Rectifier
  • Available in 20.8A @ 48Vdc
  • Power limiting and wide range AC input
  • 92% efficiency and power factor correction
  • Convection cooled
  • Hot swappable, 4RU ultra compact design


Cordex rectifiers bring advanced technology to the DC power industry. Innovative engineering combines the best in efficiency and reliability meeting the power requirements for a variety of system applications. The Cordex 1kW integrated 19" or 23" self systems with distribution is ideal for applications with lower power requirements. A compact 4RU design allows five rectifiers plus controller or six rectifiers per 19" shelf for bulk power needs. Local and remote setup, adjustment, and control is a simple single-step process with the Cordex CXC System Controller. By utilizing TCP/IP technology, complete configuration and monitoring of power equipment is possible through a network web browser.
Cordex 1kW
Electrical Specifications
Nominal Input Voltage208 to 277Vac
Operating Input Voltage150 to 320Vac
Extended Input Voltage150 to 90Vac (derated power)
Input frequency45 to 66Hz
Power output1000W continuous/module
Power factor>0.99
Efficiency>92%
Output voltage42 to 60Vdc
Output current18.5A @ 54Vdc (20.8A max.)
Load regulation<±0.5% (static)
Line regulation<±0.1% (static)
Transient response±1% for 50 to 100% load step,
2ms recovery time
Noise
Voice band<32dBrnC
Wide band<5mVrms
<100mVpk to pk
Psophometric<1mV
Noise
Voice Band<32dBrnC
Wide Band<5mVrms, <100mVp-p
Psophometric<1mV
Mechanical Specifications
Dimensions (in/mm)6.9 x 2.8 x 9.8 / 177 x 71 x 250
Weight (lb/kg)6.4 / 2.9
Features
IndicatorsAC mains OK — green LED
Module OK — green LED
Module alarm — red LED
CoolingNatural convection
Adjustments (via CXC Controller)Float and equalize voltage
Battery test voltage
High and low voltage alarms
High voltage shutdown
Current limit
Start delay timers
Slope %
ProtectionCurrent limit/short circuit
Start delay
Input/output fuses
Output high voltage shutdown
Output power limiting
Thermal foldback/shutdown
Input transient
AC low line foldback/shutdown
AC high voltage shutdown
Environmental Specifications
Operation Temperature-40 to 50°C / -40 to 122°F (with short periods up to 70°C / 158°F)
Storage Temperature-40 to 85°C / -40 to 185°F
Humidity0 to 95% non-condensing
Elevation-500 to 4000m / -1640 to 13120ft
Heat Dissipation<295BTU per hour
Standards
SafetyCSA C22.2 No 60950-1-03
UL 60950-1 1st Edition
CE marked
IEC/EN 60950-1
EMCETSI 300 386
EmissionsCFR47 (FCC) Part 15 Class B
ICES-03 Class B
EN55022 (CISPR 22) Class B
C-tick (Australia)
EN 61000-3-2
EN 61000-3-3
ImmunityEN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-4-11
ANSI/IEEE C62.41 Cat B3
Document Downloads
Title Type Version Date
Cordex 1kWr Datasheet - English (LTR) Datasheet D05 July 1, 2007
Cordex 1kWr Datasheet - English (A4 Low Res.) Datasheet D03 June 1, 2006