Did you know maintaining a tight tolerance of ±.1V on individual battery voltages provides increased battery string life?
Maximizes battery life
Replace single batteries, not the entire string
Reduces battery preventative maintenance
Spreads charge voltage equally across batteries
Compensates for battery differences as they age
Safe unattended operation designed to CSA C22.2 No. 107.1 and UL 1778 standards
Optional Potted AlphaGuard for underground battery vault applications
AlphaGuard monitors and protects your batteries by spreading the charge voltage equally across all the batteries in the string, ensuring that every battery, whether old or new, is properly charged. With an ideal voltage across each battery, life and runtime are optimized. Individual batteries in a string can be replaced as they fail, allowing good batteries to be left in service longer. This stops the wasteful and costly practice of replacing complete battery strings based on a single battery failure.
Case Study
846 battery strings totalling 2538 batteries in outside plant installations
After two years 928 batteries drift outside acceptable charging tolerance presenting a challenge during preventative maintenance visits.
At risk- 345 strings totaling 1035 batteries x $135 = $155,250
AlphaGuard investment 846 strings x $84 = $71,064
AlphaGuard reclaims lost potential of life for 928 strings
AlphaGuard
Voltage Drift by Years of Battery Life Lost
Voltage Drift by Number of Batteries
AlphaGuard
Models
AG-CMT-3:
AlphaGuard Charge Management SC, 36V - including 36Vdc battery string interface cable
AG-CMT-4:
AlphaGuard Charge Management SC, 48V - including 48Vdc battery string interface cable
Configuration
Quantity:
One (1) AlphaGuard is required per battery string
Service Location:
With the battery string
Mechanical Specifications
Housing Material:
High impact plastic
Dimensions H x W x D (in/mm):
1.4 x 4.8 x 4.3 / 36 x 122 x 108
Weight (lb/kg):
0.8/.36
Electrical Specifications
Batteries:
Individual 12Vdc nominal batteries configured into 36 or 48Vdc strings
Circuit Protection:
Fast blow fuse, reverse polarity protected
Quiescent Current Draw:
1mA max. (Current consumed by AlphaGuard after low voltage total shutdown)
Charge Management:
Most effective during float period of charge
Max. Current:
2A @ 25°C / 77°F
Quality of Final Balance:
±100mV max. between any two (2) batteries
Charging Efficiency:
80 to 90%
Charge Balance:
±100mV typical
Low Voltage Cutoff:
34.5Vdc/46Vdc ±5%
Communication to XM2:
AG-DSM cable supplies battery readings to a DSM status monitoring card
Voltage Sense Regulation:
±100mV
Environmental Specifications
Operating Temperature:
-40 to 55°C / -40 to 131°F
Humidity:
5 to 95% non-condensing
Warranty
Warranty:
5 years
Cable Options
AG-DSM-S9-Cable
AG-DSM-D9-Cable
AG-DSM-D35-Cable
AG-DSM-S35-Cable
Battery Cable 36V 6ft
Battery Cable 48V 6ft
Document Downloads
Title
Type
Version
Date
AlphaGuard Datasheet_English (A4)
Datasheet
049-225-11-004
August 10, 2007
AlphaGuard AG/CMT Installation Instructions
Manual
012-306-C0-005 Rev. E
March 5, 2008
AlphaGuard Datasheet_English (LTR)
Datasheet
049-225-10-007
August 10, 2007
Total Power Solutions™
Home
Products
About Alpha
News Room
Document Downloads
Contacts
Careers
Legal
Need Some Help?
Sitemap
Copyright © 2008 - 2012, The Alpha Group. All Rights Reserved.