AlphaGuard
  • Extends battery life
  • Replace single batteries, not the entire string
  • Spreads charge voltage equally across batteries
  • Compensates for battery differences as they age
  • Safe unattended operation designed to CSA
  • C22.2 No. 107.1 and UL 1778 standards
  • Optional Potted AlphaGuard available


AlphaGuard monitors and protects your batteries by spreading the charge voltage equally across all the batteries in the string, ensuring that every battery, whether old or new, is properly charged. With an ideal voltage always across each battery, life and runtime are optimized. Individual batteries in a string can be replaced as they fail, allowing batteries to be left in service longer. This stops the wasteful and costly practice of replacing batteries based on a scheduled maintenance programs or disposing of batteries that may have years of useful life left because one battery has failed.
General
Configuration
QuantityOne (1) AlphaGuard is required per battery string
Service LocationWith the battery string
Cabling
AG-S9-CableAG-CMT-36/48SC Voltage Sense Cable, Single String 9’
AG-D9-CableAG-CMT-36/48SC Voltage Sense Cable, Two String 9’
AG-S35-CableAG-CMT-36/48SC Voltage Sense Cable, Single String, 35’
AG-D35-CableAG-CMT-36/48SC Voltage Sense Cable, Two String, 35’
Mechanical
Housing MaterialHigh impact plastic
Dimensions (in)1.44H x 4.82W x 4.25D
(mm)36H x 122W x 108D
Weight (lb/kg)0.8/.36
Electrical
BatteriesIndividual 12VDC nominal batteries configured into 36 or 48VDC strings
Circuit ProtectionSingle blow fuse, reverse polarity protected
Environmental-40 to 55°C (-40 to 131°F), 5 to 95% humidity
Quiescent Current Draw1mA max. (Current consumed by AlphaGuard after low voltage total shutdown)
Charge ManagementMost effective during float period of charge
Max. Current2A @ 25°C
Quality of Final Balance±100mV max. between any two (2) batteries
Charging Efficiency80 to 90%
Charge Balance±100mV typical
Low Voltage Cutoff34.5VDC/46VDC ±5%
Communication to XM2AlphaGuard configured DSM status monitoring card
Voltage Sense Regulation±100mV
Document Downloads
Title Type Version Date
AlphaGuard AG/CMT Installation Instructions Manual 012-306-C0-004 Rev. D June 1, 2006
AlphaGuard Data Sheet - Chinese (A4) Datasheet 049-225-11-004 November 1, 2006
AlphaGuard Data Sheet - English (A4) Datasheet 049-225-10-007 November 1, 2006
AlphaGuard Data Sheet - English (LTR) Datasheet 049-225-10-007 November 1, 2006
AlphaGuard Data Sheet - Russian (A4) Datasheet 049-217-10-001 November 1, 2003