P45 Battery Charger
P45 Battery Charger
  • Microprocessor control
  • Provides regulated DC output and current limiting capabilities
  • Graphical interface
  • Wide temperature range 0 to 50°C / 32 to 122°F
  • Approved for UL, CE, CSA and EMC standards


Various filtering levels are available to match output requirements. Typical MTBF is 100,000 hours and typical MTTR is less than one hour. The charger’s graphic interface, with its user-definable controls and alarm set-points, allows for quick and versatile customization. Operates to UL, CE, CSA and EMC standards.
P45 Battery Charger
Standard Features
Metering and Timing0.5% accuracy DC voltage and current metering
Remaining and elapsed equalize time
Control ModesManual float/equalize toggle
Control AdjustmentsFloat and equalize voltage
Current limit
Equalize period 0 to 100 hours
Float period 0 to 100 days
Equalize mode termination based on voltage, time and/or low DC volts event(s)
Indicating LEDsAC On—green LED
Common alarm—flashing red LED
Alarm Menu IndicationsCharger failure based on low volts and low output DC current
High DC volts
Low DC volts
Positive ground fault
Negative ground fault
AC fail
Alarm Menu Functions (password protected)Adjustable alarm time delay
Indications latch
Alarm relays latch
Alarm acknowledgment
Alarm levels adjustment
LED, LCD and relay test
Remote indicationsAll alarms are wired to a common voltage free N.O. and N.C. dry contacts
Optional Features
Individual alarms form C contacts
RS 232/485 communication ports
Modbus on serial ports
SNMP interface
DC circuit breaker
Negative temperature compensation 0.2%/°C
Battery circuit breaker
Distribution panel
High capacity interrupting current CBs
High temperature alarm and shut-down
High volts shutdown via AC breaker trip
AC input volts, amps and frequency readings
High and low AC input voltage alarm
High ripple alarm
Power factor correction to 0.95 lagging
Tropicalization
Remote voltage sensing terminals
Remote shutdown and equalize control
Audible alarm
Manual voltage control
Input harmonic filter to comply with CE
50Hz or 400Hz input frequency
Low DC volts load disconnect (load shedding)
End of discharge alarm
Negative slope for equal load sharing
Battery discharging alarm
Battery high temperature alarm and shutdown
Battery ammeter and voltmeter
Ampere-hour meter reading battery capacity % or AH
DC distribution panel
Oversized cabinets to fit batteries in separate compartments
Special paint and NEMA / IP protection
Seismic design
Fungus proofing and tropicalization
Special wiring
Document Downloads
Title Type Version Date
P45 Data Sheet - English (LTR) Datasheet 049-215-36-003 October 1, 2005
P45 Series Battery Charger Operating Manual Manual 031-186-B1-001 Rev. A June 1, 2006
P45 Series Battery Charger Technical Manual Manual P45CHARGER-SCR February 1, 2007