AlphaCell 85 GXL-HP
Designed specifically for standby applications
Deliver 100% out-of-box capacity - no cycling required
Full replacement, non-prorated warranties
True Gel Silver Alloy minimizes grid corrosion
Maintenance-free threaded inserts; no periodic retorquing
Provides maximum runtime over the life expectancy of the battery
Industry leading runtime for Voice Over IP networks
Alpha’s standby battery offering incorporates true Gel Cell and Silver Alloy grid battery technologies, ensuring optimal performance for your outdoor cable, traffic or WiFi application. AlphaCell batteries provide the ultimate warranty, longest runtimes and superior longevity in today’s demanding outdoor non-temperature controlled cable power environments.
AlphaCell 85 GXL-HP
General Specifications
Warranty:
5 years
Service Life:
Extended
Runtime (minutes):
85
VRLA Battery Type:
Gel Silver Alloy
Heat Resistant:
Extreme
Hydrogen Emission:
Low
Terminals:
Threaded insert 10 - 32 UNF
Cells Per Unit:
6
Voltage Per Unit:
12.8
Conductance Value:
600
Max. Discharge Current (A):
600
Short Circuit Current (A):
2200
10 Second Volts @ 100A:
10.8
Ohms Impedance 60Hz:
0.0065
Capacity at 20hrs (to 1.75VPC):
50AH
BCI Group Size:
22
Weight (lb/kg):
39.6/18
Dimensions H x W x D (in/mm):
8.1 x 9 x 5.5 / 206 x 228 x 139
Operating Temperature Range
Discharge:
-40 to 71°C (-40 to 160°F)
Charge (with temp compensation):
-23 to 60°C (-9.4 to 140°F)
Float Charging Voltage @ 25°C / 77°F:
13.5 to 13.8Vdc
AC Ripple Charger:
0.5% RMS or 1.5% of float charge voltage recommended for best results. Max. allowed = 4%V pk to pk
Document Downloads
Title
Type
Version
Date
Battery Recycling Information Sheet
Datasheet
049-018-78-001
June 1, 2010
AlphaCell 85GXL HP Datasheet_Eng
Datasheet
049-326-10-A001
June 1, 2009
AlphaCell Gold and GXL MSDS - ENG
Advisory
049-018-29-004
July 28, 2009
AlphaCell MSDS Sheet - Spanish
Advisory
2009
August 1, 2009
Connecting Battery Cable kits to Threaded Insert Terminals on AlphaCell Batteries
Advisory
875-607-C0-001 Rev. A
January 1, 2007
AlphaCell Gel Cell Battery Users' Guide (Storage, Maintenance and Deployment)
Manual
745-680-C0-002 Rev. B
October 16, 2009
You might also be interested in these other Alpha products:
AlphaGuard™
Battery Charge Management
Node Power Supply (NPS) Enclosure
Indoor/Outdoor Power System Enclosure
XM2-HP Series
Energy Efficient CableUPS®
Total Power Solutions™
Home
Products
About Alpha
News Room
Document Downloads
Contacts
Careers
Legal
Need Some Help?
Sitemap
Copyright © 2008 - 2012, The Alpha Group. All Rights Reserved.