Select Your Country
Cordex CXPS 48-1T
Cordex CXPS 48-1T
  • 48Vdc systems using high density 3.6kW rectifiers
  • Front access DC connections
  • CXCM4 advanced modular controller
  • Flexible integrated rack options
  • Optional DC to DC converter upgrade kits
  • Integrated system shunt and LVD


Argus CXPS standard power systems bring proven Cordex technology into a standard integrated system package. The CXPS 48-1T uses high density 48V-3.6kW rectifiers, the front access single-tier distribution, and the advanced CXCM4 digital controller. Perfect for both wireline and wireless applications, the CXPS 48-1T provides up to 375 Amps of 48VDC power, and allows for future expansion of up to 600 Amps via an additional rectifier shelf. Optional DC-DC converter kits are available for quick integration to provide dual 48V/24V output operation. The CXPS 48-1T can be integrated easily into customer provided relay racks or enclosures. This system can also be easily ordered factory-installed into various Argus rack configurations including a system with pre-wired battery trays.
CXPS 48-1T
Configurations
053-392-20-000Base system with 23" mounting
053-392-20-010System mounted in 22RU (1/2 height) battery mount rack
053-392-20-020System mounted in 44RU Zone 4 seismic rack
053-392-20-030System mounted in 44RU Zone 4 seismic rack with 3x battery trays for 3x 48V strings
RectifierUp to 5x 48V-3.6kW rectifier positions
Distribution18x AM plug-in breaker positions
10x GMT type fuse positions
Shunt
Low voltage disconnect
ControllerCXCM4 modular controller
Electrical Specifications
Input Voltage176 to 320Vac
Current16.8A @ 240Vac nominal (per rectifier module)
Frequency45 to 66Hz
Power Factor>0.99
Output Voltage42 to 60Vdc
CurrentSystem 375A (expandable to 600A with additional CXRF shelf)
Rectifier75A @ 48Vdc
PowerSystem 18kW (expandable to 28.8kW with additional CXRF shelf)
Rectifier 3600W max
Envrionmental Specifications
Temperature-40 to 65°C / -40 to 146°F
-40 to 75°C / -40 to 167°F derated output
Humidity0 to 95% non-condensing
Elevation-500 to 2800m / -1640 to 9186ft
-500 to 4000m / -1640 to 13124ft with derated output
Mechanical Specifications
Dimensions (in/mm)19.25 x 23 x 18.8 / 488 x 584 x 477
Mounting23" center mount
Weight (lb/kg)110 / 49.8
Connections
Load BreakerHot 1/4"-20 studs on 5/8" centers
Return 1/4" holes on 5/8" centers
GMT FusesScrew terminal 1.31mm2 to 0.128mm2 (#16 to #26 AWG)
Battery Terminations3/8" holes on 1" centers
4x Sets per polarity
Rectifier Input3/8" holes on 1" centers
Alarm ConnectionsScrew terminal 1.31mm2 to 0.128mm2 (#16 to #26 AWG)
AccessCable top or bottom
User front access after installation
Related Components
010-567-20Cordex 48V-3.6kW rectifier
038-276-20CSM02 DC-DC converter kit
Document Downloads
Title Type Version Date
Cordex CXPS 48-1T Datasheet_Eng (LTR) Datasheet 048-713-10_E01 November 1, 2007
Cordex CXPS 48-1T Datasheet_Eng(LTR) Datasheet 048-713-10 November 1, 2007