Select Your Country
Cordex 400W
Cordex 400W
Cordex rectifiers feature some of the most innovative DC power technology today. Expert engineering combines the maximum in efficiency and reliability into one compact unit. The new Cordex series have power density improvements of 200-300% over previous rectifiers and incorporate many new features. Cordex rectifiers are available in a wide array of power sizes from 250 to 3600W per module, offering the most compact and cost effective power system design. Multiple DC output and AC input options are available to provide an ideal solution for most telecommunications and utility applications. Combining a unique blend of advanced features, high reliability and greater efficiency, Cordex rectifiers offer significant operational and capital savings. High power diversity modules provide users with greater rack space for additional revenue generating equipment in space-restricted environments. Fan cooled rectifier options are industry leading in terms of high temperature operation in harsh environments including outdoor enclosure solutions. Cordex rectifiers are designed to operate seamlessly with the Cordex CXC system controllers for advanced configuration and local or remote system control and monitoring.
Cordex 400W
Electrical Specifications
Part number010-582-20
Input voltage90 to 320VAC
Input frequency45 to 70Hz
Power factor>99%
THD<5%
Efficiency>90%
Power output400W (max)
Output voltage20 to 29VDC
Output current14A (current limited)
Load regulationStatic <±0.5%
Dynamic <±2% for 50 to 100% load step
2ms recovery time
Line regulationStatic <±0.1%
Dynamic <±1% for any change within rated limits
Wide band noise<30mVrms
<150mVp-p
Psophometric noise<1mV
Mechanical Specifications
Dimensions
mm88.4H x 71.6W x 242D
inches3.4H x 2.8W x 9.5D
Weight1.4kg (3lb)
Features
IndicatorsAC mains OK — green LED
Module alarm — red LED
CoolingNatural convection
AdjustmentsFloat and equalize voltage (via CXCI controller) Battery test voltage
High and low voltage alarms
High voltage shutdown
Current limit
Start delay time
Slope %
ProtectionCurrent limit/short circuit
Input/output fuses
Output high voltage shutdown
Output power limiting
Thermal foldback/shutdown
Input transient
AC low line foldback/shutdown
AC high voltage shutdown
Environmental Specifications
Temperature
Operation-40 to 50°C (-40 to 122°F)
(power de-rated up to 70°C/158°F)
Storage-40 to 85°C (-40 to 185°F)
Humidity0 to 95% RH non-condensing
Elevation-500 to 3000m (-1640 to 9840ft)
Heat dissipation<94BTU per hour
Standards
The Cordex 400W is designed to meet the following
SafetyCSA C22.2 No 60950-1-03
UL 60950-1 1st edition
CE marked
IEC/EN 60950-1
EMCETSI 300 386
EmissionsCFR47 (FCC) Part 15 Class B
ICES-03 Class B
EN55022 (CISPR 22) Class B
C-Tick (Australia)
EN 61000-3-2
EN 61000-3-3
ImmunityEN 61000-4-2
EN 61000-4-3
EN 61000-4-4
EN 61000-4-5
EN 61000-4-6
EN 61000-4-11
ANSI/IEEE C62.41 Cat B3
Document Downloads
Title Type Version Date
Cordex 400Wr Datasheet - English (A4 Low Res.) Datasheet D03 June 1, 2006
Cordex 400Wr Datasheet - English (LTR Low Res.) Datasheet D04 May 1, 2007