Alpha Technologies Inc.
Phone: 360 647 2360
Email: alpha@alpha.com
Celltron Essential
Celltron Essential

Prolong the life of your battery network and keep your customers connected.

  • Complete battery life trending through conductance tests
  • One-step, non-intrusive conductance measurements do not reduce string life
  • Quick, accurate measurements and data recording reduce on-site time
  • Simple pinpoint testing requires only access to two battery posts or straps
  • Enables early detection of questionable batteries in the network


A fast, reliable and affordable testing process is now available with the development of conductance based battery measurement technology. By coupling conductance testing with a simple system load or voltage test, the system operator is armed with the quality of data necessary to know the status of their installed standby batteries and budget their replacement with confidence.
Celltron Essential
Nominal Specifications
Model Number:CTE-1200AT (w/ temp sensor)
Applications:Tests 6 and12V batteries with data retention
Voltage:1.5 to 20Vdc
Conductance:100 to 9,999 Siemens
Test Data Storage:Up to 144 consecutive tests can be stored internally
Accuracy:+/-2% across test range
Voltmeter Resolution:10mVdc
Environmental Specifications
Operating Temperature:0 to 40°C / 32 to 104°F
Humidity:95% non-condensing
Conductance Technology
IEEE Standards 1188 & 484
EPRI Guide for testing stationary batteries
Guide for Testing Stationary Batteries International
Telecommunications Energy Conference
Bellcore T1Y1
Presentation for American National Standards Institute
International Lead Zinc Research Organization
Battery Council International
Applications
Cable TV/Broadband Power Networks
- Outside Plant Batteries - Headend DC/AC Batteries - Premise Back Up Supplies (FTTx)
6/12V, 5 to 600AH Stationary Batteries
Security System Batteries
Emergency Lighting Batteries
Features and Benefits
Simple - One-step testing, no instrument inputs or adjustments required.
Quick - Battery voltage and conductance displayed in less than 10 seconds. Test an entire 48V string in less than 1 minute.
Safe - Utilizes patented conductance technology, a passive method that minimizes technician risk.
Accurate - Field test proven to ±2% accuracy across test range. Conductance method recognized by IEEE standard for the testing of lead-acid batteries with proven correlation to battery capacity.
Economical - Efficient and accurate battery tester priced to fit into every technician’s tool kit.
Celltron Essential CET-1200AT
Kit Contents
Contains:CTE-1200AT tester
PowerSure Software
Infrared PC data cable
Optional Equipment:Handheld Printer
Infrared Module for PC
Celltron Essential
AlphaCell Batteries
Models:Siemens/Mhos
85GXL600
165GXL1000
185GXL / 195 Gold-HP1100
160A1300
220GXL / 220 Gold-HP1200
Document Downloads
Title Type Version Date
Celltron Essential Instruction Manual_Eng (LTR) Manual 168-357A March 25, 2008
AlphaCell Testing Data Sheet - English (LTR) Datasheet 049-018-42-004 March 1, 2006
Digital Midtron Quick Reference Guide Manual DM-3200 AT March 1, 2007
AlphaCell Testing Data Sheet - English (A4) Datasheet 049-018-43-004 March 1, 2006