Alpha Technologies Inc.
Phone: 360 647 2360
Email: alpha@alpha.com
Celltron Advanced Kit
Celltron Advanced™
  • Complete battery life trending through conductance tests
  • Non-intrusive conductance measurements do not reduce string life
  • Quick, accurate measurements and data recording reduce on-site time
  • Simple pinpoint testing requires only access to two battery posts or straps
  • Enables early detection of questionable batteries in the network


A fast, reliable and affordable testing process is now available with the development of conductance based battery measurement technology. By coupling conductance testing with a simple system load or voltage test, the system operator is armed with the quality of data necessary to know the status of their installed standby batteries and budget their replacement with confidence.
Celltron Advanced
Nominal Specifications
Model Number:CTA-4000 (kit)
CTA-2000 (analyzer only)
Applications:Tests individual lead acid cells or monoblocs (up to 16V) in any common configuration
Voltage:1 to 20Vdc
Conductance:100 to 9,999 Siemens
Test Data Storage:16 string locations of 480 test results stored internally
Accuracy:+/-2% across test range
Voltmeter Resolution:5mVdc
Environmental Specifications
Operating Temperature:0 to 40°C / 32 to 104°F
Humidity:95% non-condensing
Conductance Technology
IEEE Standards 1188 & 484
EPRI Guide for testing stationary batteries
Guide for Testing Stationary Batteries International
Telecommunications Energy Conference
Bellcore T1Y1
Presentation for American National Standards Institute
International Lead Zinc Research Organization
Battery Council International
Applications
Cable TV/Broadband Power Networks
- Outside Plant Batteries - Headend DC/AC Batteries - Premise Back Up Supplies (FTTx)
6/12V, 5 to 600AH Stationary Batteries
Security System Batteries
Emergency Lighting Batteries
Features and Benefits
Simple - One-step testing, no instrument inputs or adjustments required.
Quick - Battery voltage and conductance displayed in less than 10 seconds. Test an entire 48V string in less than 1 minute.
Safe - Utilizes patented conductance technology, a passive method that minimizes technician risk.
Accurate - Field test proven to ±2% accuracy across test range. Conductance method recognized by IEEE standard for the testing of lead-acid batteries with proven correlation to battery capacity.
Economical - Efficient and accurate battery tester priced to fit into every technician’s tool kit.
Celltron Advanced Kit CTA-4000AT
Kit Contents
Contains:Protective boot
Rechargeable battery pack
Infrared PC data receiver and software
Infrared printer
Infrared temperature sensor
Protective carrying case
Both clamp and probe cables
Spare fuses, printer paper, probe tips
Optional Equipment:Handheld Printer
Infrared Module for PC
Document Downloads
Title Type Version Date
Celltron Advanced Quick Reference Guide Manual CTA-4000 AT March 1, 2007
AlphaCell Testing Data Sheet - English (LTR) Datasheet 049-018-42-004 March 1, 2006
Digital Midtron Quick Reference Guide Manual DM-3200 AT March 1, 2007
AlphaCell Testing Data Sheet - English (A4) Datasheet 049-018-43-004 March 1, 2006