Hardware| RF Cable Interface | F-connector, female, 75 0hm |
|---|
| Local Interface | RJ-12, RS-232, 19.2kb,N,8,1 |
|---|
| Requires serial port adapter and PC with terminal emulation software |
|---|
| (Hyper-Terminal recommended) |
|---|
| LED Indicators | Transponder Ready/RF Link Established |
|---|
| Transponder/CMTS Communications |
|---|
| Power Supply/Transponder Communication |
|---|
| Environmental | -40° to 65°C / -40° to 149°F, 10 to 90% non-condensing humidity |
|---|
| Emissions | EN50022 Class A and FCC Part 15 Class A (Installed in power supply enclosure system) |
|---|
Monitored Parameters| Number of Power | Up to six, each reporting individual data |
|---|
| Power Supply Data | Major Alarm (includes Test fail, Battery fail, Line Isolation, Output overload/fault, Over temp, N+1 active, fuse fail) |
|---|
| Minor Alarm (includes temp probe error, AC line loss, N+1 error) |
|---|
| • Input AC Line Voltage |
|---|
| • Output Voltage |
|---|
| • Output Current 1 |
|---|
| • Output Current 2,3,4 (if installed) |
|---|
| • Output Power |
|---|
| • Power Supply Status (line, standby, test in progress, test alarm) |
|---|
| • Enclosure Door (open/closed) |
|---|
| Power Supply Control | Remote test start/stop |
|---|
| Number of Battery String | One or two Strings of 36V or 48V |
|---|
| Additional battery string monitoring available |
|---|
| Call Alpha for more information |
|---|
| Battery Data | Individual battery voltages |
|---|
| Battery compartment temperature |
|---|
| Generator Data | • Status (off, running, alarm) |
|---|
| (Alarm includes low oil pressure, engine over-temp, engine over-speed, crank limit, over voltage, low fuel, water intrusion, pad shear, gas hazard, test fail) |
|---|
| • Gas Hazard |
|---|
| • Water Intrusion |
|---|
| • Pad Shear |
|---|
| • Enclosure Door (open/closed) |
|---|
| • Ignition Battery Voltage |
|---|
| • Enclosure Temperature |
|---|
| • Low Fuel |
|---|
| Generator Control | Remote test (start/stop) |
|---|