AlphaGuard monitors and protects your batteries by spreading the charge voltage equally across all the batteries in a string, ensuring that every battery in the string, whether old or new, is properly charged. With an ideal voltage always across each battery, life and runtime are optimized. Individual batteries in a string can be replaced as they fail, allowing batteries to be left in service longer. This stops the wasteful and costly practice of disposing of batteries that may have years of useful life left because one battery in a string fails or replacing batteries based on a scheduled maintenance program. With the optional communications cabling and interface module individual battery measurements are made at the batteries and reported, improving accuracy and allowing the power supply to determine End-of-Discharge by individual batteries instead of the string voltage and reporting to status monitoring systems. The Potted Alpha Guard model is ideal for applications where batteries are installed below grade and subject to damp conditions or possible immersion.
General
Configuration
QuantityOne (1) AlphaGuard is required per battery string
Service LocationWith the battery string
Cabling
AG-S9-CableAG-CMT-36/48SC Voltage Sense Cable, Single String, 9’
AG-D9-CableAG-CMT-36/48SC Voltage Sense Cable, Two String, 9’
AG-S35-CableAG-CMT-36/48SC Voltage Sense Cable, Single String, 35’
AG-D35-CableAG-CMT-36/48SC Voltage Sense Cable, Two String, 35’
Mechanical
Housing MaterialHigh impact epoxy
Dimensions (in)1.44H x 4.82W x 4.25D
(mm)36H x 122W x 108D
Weight (lb/kg)1.5/.67
Electrical
BatteriesIndividual 12VDC nominal batteries configured into 36 or 48VDC strings
Circuit ProtectionSingle blow fuse, reverse polarity protected
Environmental-40 to 55°C (-40 to 131°F), 5 to 95% humidity
Quiescent Current Draw1mA max. (Current consumed by AlphaGuard after low voltage total shutdown)
Charge ManagementMost effective during float period of charge
Max. Current2A @ 25°C
Quality of Final Balance±100mV max. between any two (2) batteries
Charging Efficiency80 to 90%
Charge Balance±100mV typical
Low Voltage Cutoff34.5VDC/46VDC ±5%
Communication to XM2AlphaGuard configured EDSM communications card