Alpha Technologies Inc.
Phone: 360 647 2360
Email: alpha@alpha.com
AlphaCell FT
  • Front terminal design with protective covers
  • High power density
  • Used for both telecom and cable applications
  • Gel long life batteries can be used in outdoor applications


Alpha enhances its AlphaCell battery family to include the FT Series of front terminal batteries for cable television and telecommunication applications. The AlphaCell FT series are valve regulated lead acid batteries and designed for long life. Benefi ts of these new batteries include: central gassing system, hinged front covers, integral fl ame arrestor, recyclable lead and plastics and low self discharge rates. These batteries come with a handle for carrying convenience.
AlphaCell FT
General Specifications
Model:195 GXL-FT225 AGM-FT
Warranty (Optional extended warranties available):
Standard:3 year full replacement3 year full replacement
For batteries in service below 38th parallel:2 year full replacement2 year full replacement
Service Life:ExtendedExtended
Sealed VRLA:Valve regulated lead acidValve regulated lead acid
Heat Resistant:HighModerate
Hydrogen Emission:LowLow
Terminals:16mm Insert M6 thread16mm Insert M6 thread
Case Material:ABS (VO on request)ABS (VO on request)
Battery Type:Gelled ElectrolyteAbsorbed Glass Mat
Typical Runtime (min):195225
Cells Per Unit:66
Voltage Per Unit:12.812.8
Conductance Value (Using Midtronics Meter):12001400
Max. Discharge Current (A):400400
Short Circuit Current (A):30003100
10 Second Volts @ 100A:10.811.2
Ohms Impedance 60Hz:4.1mOhms4.5mOhms
Capacity at 20hrs(to 1.75VPC):110Ah115Ah
Weight (lb/kg):76.29/34.5275.14/34
Height with terminals (in/mm):11.22/28511.22/285
Width (in/mm):4.33/1104.33/110
Depth (in/mm):15.55/39515.55/395
Operating Temperature Range
Discharge (C):-40 to 71°C (-40 to 160°F)-40 to 71°C (-40 to 160°F)
Charge (with temp compensation)(C):-20 to 50°C (-4 to 122°F)-20 to 50°C (-4 to 122°F)
Float Charging Voltage (VDC):Float 2.27 to 2.30VPC @25°CFloat 2.27 to 2.30VPC @25°C
Cycling 2.35VPC @25°CCycling 2.35VPC @25°C
AC Ripple Charger:0.5%RMS or 1.5% of float charge voltage recommended for best results. Maximum allowed = 4%V pk to pk
Document Downloads
Title Type Version Date
AlphaCell FT Datasheet_Eng Datasheet 049-018-47-003 October 22, 2010
MSDS Sheet for AlphaCell FT Batteries - English (LTR) Brochure February 1, 2006
AlphaCell Testing Data Sheet - English (LTR) Datasheet 049-018-42-004 March 1, 2006
AlphaCell Testing Data Sheet - English (A4) Datasheet 049-018-43-004 March 1, 2006
AlphaCell Gel Cell Battery Users' Guide (Storage, Maintenance and Deployment) Manual 745-680-C0-002 Rev. B October 16, 2009


You might also be interested in these other Alpha products:
AlphaGuard™
Battery Charge Management