Select Your Country
AlphaGen 7.5kW Telecom
AlphaGen 7.5kW Telecom
  • Cost effective extended runtime solution for outdoor powering applications
  • Quiet operation, small size, and low profile allow for easier installation in populated areas
  • Eliminates large quantities of batteries otherwise required for extended runtime
  • Telecom grade 48Vdc output


The AlphaGen curbside generator system is specifically designed for outside plant communication networks. Every AlphaGen system incorporates industry leading power technology, including: natural gas or propane powered engine generators, exclusive audible noise baffling, remote status monitoring features, and durable weather resistant enclosures. Alpha offers a full line of AlphaGen systems specifically designed for telecom applications.
AlphaGen 7.5kW Telecom
General Specifications
DC Output Voltage52.0V ±0.5V @ no load 48V configuration
104.0V ±0.5V @ no load 96V configuration
DC Output Load Regulation0.5V
Output Current52.0V @ 144A max.
104V @ 72A max.
Engine624CC, Air cooled, Twin OHV
15hp (using natural gas fuel)
RPM(Variable Speed)2800 to 3600RPM
Acoustical Noise
dBA 10' @ 100% Rated Load70.3
dBA 20' @ 100% Rated Load64.3
dBA 10' @ 70% Rated Load66.4
dBA 20' @ 70% Rated Load60.4
Mechanical Specifications
PN-6x
Dimensions (in/cm)39 (57 with optional pedestal) x 39.25 x 24 / 99 (144) x 100 x 61
Weight (lb/kg)338 / 174 (370/168 with optional pedestal)
APU Fuel Consumption
Natural Gas1000BTU/ft.3156ft3/hr
Propane Gas 2520BTU/ft.31.48 gal/hr to 54ft3/hr to 6.24lb/hr Exterior Surface TemperatureMeets requirements of UL/CSA
Specifications
Gas Inlet Pressure0.5 to 2 PSI Inlet Pressure (Contact Alpha Engineering for additional supply resources)
Ign Charger Voltage13.5Vdc
Ign Charger Current6A max
Remote Interface Length75ft max. Distance depends upon installation, derating and wire gauge
StandardsUL1778, UL2200, NFPA 37/54/58 and 70, CSA C22.2 No.107.1, EMC/FCC Part 15 Class A
Features
Fuel System, Controls and MonitoringThe controls and fuel system meet applicable sections of NFPA 37, 54 and 58 for automatic unattended operation of remotely located generators. Full System Control and Status Monitoring included.
SensorsGas Hazard, Pad Shear, Water Intrusion and Tamper
Safety ShutdownsLow Oil Pressure, Low Fuel Pressure Shutdown (Propane only), Over Temp, Water Intrusion,
Pad Shear, Gas Hazard (Propane or Natural Gas), Over-Speed, Over-Crank
Optional FeatureCold Start Kit Provides additional starting capability at temperatures below -18°C / 0°F
Document Downloads
Title Type Version Date
AlphaGen Telecom Data Sheet (LTR) Datasheet 049-095-13-005 February 1, 2006
AlphaGen Technical Manual_Eng Manual 042-288-B0-001 Rev. A May 1, 2008