Select Your Country
24V Remote Solar Power Systems
24V Solar Power Systems
  • Cost-effective alternative to AC line extension
  • Reliable power where you need it, when you need it
  • Minimum of six days of design load autonomy
  • Engineered for pole or pad mounting, and rapid field deployment


Applications include: Security systems, traffic systems, emergency power, cathodic protection, navigational aids, WiMax and SCADA.

Solar Power Systems (SPS) can be configured to provide a range of DC or AC power outputs. Systems include the most recent advances in PV manufacturing, electronic controls and power management. Standard controls include temperature-compensated 3-stage battery charging, battery low voltage disconnect, lightning protection and complete circuit protection. Each system comes with a two-year limited warranty (extended warranties are available), while the PV modules carry a 20 to 25-year performance guarantee.

The SPS design incorporates a minimum of six days load autonomy, providing reliable power with no operational or maintenance costs and near-zero annual load loss probability. Systems are engineered for pole or pad mounting and packaged for easy installation.

Options Include: Multiple output breakers, data logging of system operating parameters, alarm outputs for critical system parameters, DC to AC inverter for AC loads and additional enclosure for customer use.
Solar Power Systems
Specifications
SPS24-108GSPS24-340/216GSPS24-440/255G
Electrical Specifications, Solar Panel
Maximum Power170W340W440W
Power Tolerance+-5%+-5%+-5%
Maximum Power Voltage35Vdc35Vdc34.6Vdc
Maximum Power Current4.86A4.86A3.18A
Open Circuit Voltage44.0Vdc44.0Vdc43.4Vdc
Open Circuit Current5.36A5.36A3.47A
Maximum System Voltage600Vdc600Vdc750Vdc
Nominal Operating Cell Temperature47° C, +-2° C47° C, +-2° C47° C, +-2° C
Operating Temperature-40° C to +90° C-40° C to +90° C-40° C to +90° C
Dielectric Isolation Voltage1000Vdc1000Vdc1000Vdc
Maximum Wind Resistance60m/s60m/s60m/s
Maximum Hail Diameter @ 80km/h25mm25mm25mm
Mechanical Specifications, Solar Panel
Length(in/mm)62.20/158062.20/158051.96/1320
Width(in/mm)31.81/80831.81/80825.98/660
Depth(in/mm)1.81/461.81/461.37/35
Weight(kg/lb.)16/35.216/35.210.5/21.3
FrameAluminumAluminumAluminum
Front SideGlass, 3.2mmGlass, 3.2mmGlass, 3.2mm
EncapsulantEVAEVAEVA
Cell TypeSingle Crystal CellSingle Crystal CellSingle Crystal Cell
Number Cells72 in Series72 in Series72 in Series
General Specifications, Rack
Angle15 to 60° from Horizontal0 to 90°0 to 90°
PoleCustomer Supplied 2.5” Schedule 40 or 80Customer Supplied 3” Schedule 40 or 80Customer Supplied 3” Schedule 40 or 80
Electrical Specifications, Solar Controller
Rated Solar Input10A20A20A
Rated Load10A20A20A
Current Overload25% for 5 minutes25% for 5 minutes25% for 5 minutes
Regulated Output Voltage28.2Vdc28.2Vdc28.2Vdc
Load Disconnect23Vdc23Vdc23Vdc
LVD Reconnect25.2Vdc25.2Vdc25.2Vdc
Temperature Compensation-56 mV/° C-56 mV/° C-56 mV/° C
Self-Consumption6 to 10mA6 to 10mA6 to 10mA
Operating Temperature-40 to +85° C-40 to +85° C-40 to +85° C
Battery ChargerTrue 0 to 100% PWM duty cycleTrue 0 to 100% PWM duty cycleTrue 0 to 100% PWM duty cycle
Setpoint accuracy< 35mV< 35mV< 35mV
General Specifications, Battery
Voltage12V (nominal)12V (nominal)12V (nominal)
Capacity108 Ah at the 100 hour rate, to 1.75 VPC at 27° C (80° F)215 Ah at the 100 hour rate, to 1.75 VPC at 27° C (80° F)255 Ah at the 100 hour rate, to 1.75 VPC at 27° C (80° F)
TypeGelGelGel
Plate AlloyLead CalciumLead CalciumLead Calcium
Element, Post3/8” x 16 Stainless Steel Stud Posts3/8” x 16 Stainless Steel Stud PostsOffset Post with Horizontal Hole, Stainless Steel 5/16" Bolt and Hex Nut
Mechanical Specifications, Integrated Control/Battery Enclosure
Size24x25x14 (PWE-3)24x25x14 (PWE-3)24x25x14 (PWE-3)
Weight (lb.)214388473
Solar Power System
Features
Minimum of six days of design load autonomy
No routine operational and maintenance costs
Engineered for pole or pad mounting, and rapid field deployment
Rugged aluminum control/battery enclosure
Cost-effective alternative to AC line extension
Reliable power where you need it, when you need it!
Options
Output voltage regulation
Multiple output breakers
Data logging of system operating parameters
Alarm outputs for critical system parameters
DC to AC inverter for AC loads
Additional enclosure for customer use
Document Downloads
Title Type Version Date
SPS Systems Data Sheet_Eng Datasheet 049-238-13-003 February 1, 2008