AlphaNet DSM and ESM
  • Network connectivity for the Alpha XM2, XM2VP and GMX Broadband UPS power supplies, no additional power supply interface cards required
  • Supports standard networking protocols including SNMPv1 and v2c
  • Embedded Web server for advanced diagnostics
  • Embedded DOCSIS or EuroDOCSIS cable modem or direct Ethernet interface
  • Monitors up to four strings of 36V or 48V batteries
  • Standard ANSI/SCTE power supply and generator MIBs
  • Local port provides on-site technician access


Alpha’s AlphaNet family of networking products, including the DOCSIS and Ethernet Status Monitor (DSM and ESM) broadband power communication cards enable Alpha’s XM2 and GMX UPS’s to connect directly to a network using the DOCSIS communication protocol. Advanced features and networking services enable quick reporting and access to critical powering information to keep your broadband network running.

The AlphaNet family of products supports all standard networking protocols and standards required for effective power network management. Through a Simple Network Management Protocol (SNMP) interface, standard MIBs are used for quick, efficient network status and diagnostics. A Web interface enables any authorized personnel direct access to powerful, advanced diagnostics using a common web browser. A single DSM/ESM installed in an XM2 or GMX can support communications and system control for multiple power supplies and an AlphaGen™ backup generator system. When combined with an AlphaGuard™ battery balancing system, battery voltage measurements and battery charge management are accomplished through a single wire harness for simplified installations.
Specifications
Interface
Power Supplies SupportedXM2, XM2VP, GMX
Network ConnectionRJ-45, MDI standard 10 BASE-T auto-sensing (ESM models only)
RF ConnectionF-connector, female, 75 ohm (DSM models only)
LED IndicatorsAlarm, Ready, Comm, Link, DS, REG
Tamper2-pin header
Battery Input A/B8-pin, female connector, string A and B, 36V or 48V monitoring
Battery Input C/D8-pin, female connector, string C and D, 36V or 48V monitoring (optional)
Alpha Bus Multi-Device CommunicationsRJ-12 offset, RS-485 multidrop, communication and system control for multiple XM2’s and an AlphaGen
Local PortRJ-12, RS-232, 19.2,N,8,1
Requires serial port adaptor for laptop connection
Access to power supply MIB data and
network parameters
Electrical/Mechanical/Environmental
Operating Temperature-40° to 65°C / -40° to 149° F
Storage Temperature-40° to 85°C / -40° to 185° F
Humidity10 to 90% non-condensing
EmissionsEN50022 Class A1 FCC Part 15 Class A1
Network Communications
Network ProtocolsIP, UDP, TCP, DHCP, TFTP
SNMPv1, v2c
Embedded Web InterfaceRead access MIB variables, Read-Write access networking parameters
MIBsPower Supply (ANSI/SCTE 38-4)
Generator (ANSI/SCTE 38-6)
Property (ANSI/SCTE 38-1)
Alpha Proprietary Advanced UPS Diagnostics
Monitored Parameters
Major AlarmLogical (OR) of test fail, battery fail, line isolation
alarm, output overload, inverter over temperature, N+1 active, fuse fail
Minor AlarmLogical (OR) of temperature probe error, AC line loss, N+1 error
Input Line Voltage90-270Vac 50/60Hz measured value
Output Voltage60/90Vac measured value
Output Current 10 to 25A measured value
Output Current 2,3,40 to 25A measured value (if optional ports installed)
Output PowerCalculated, reported in AC Watts
UPS StatusAC line, Standby, Test in-process, Test Alarm
Enclosure DoorOpen/Closed
Battery Voltage6V or 12V batteries, up to 16 batteries Individual
battery voltages measured reported to ±100mv
resolution
Battery TemperatureMeasured, reported in Celsius
Remote Test ControlStart/Stop XM2 self test cycle
Generator Monitored Parameters
StatusOff, Running, Alarm
AlarmLogical (OR) of low oil pressure, engine over
temperature, engine over speed, crank limit, over voltage,
low fuel, water intrusion, pad shear, gas hazard, test fail
Gas HazardIndicates combustible fumes above acceptable levels (LEL)
Water IntrusionGenerator compartment flooded
Pad ShearGenerator has been dislocated
Enclosure DoorOpen/Closed
Ignition Battery VoltageMeasured value for 12V generator battery. Reported to ±100mv resolution
Enclosure TemperatureMeasured temperature inside generator compartment
Low FuelIndicates fuel level insufficient to sustain engine
Remote Test ControlStart/Stop generator self test cycle
Embedded Cable Modem (DSM Models Only)
StandardsDOCSIS 2.0, EuroDOCSIS 2.0
Tx Frequency Range5 to 42MHz DOCSIS, 5 to 65MHz EuroDOCSIS
Output Power8 to 58dBmV
Channel Bandwidth6MHz DOCSIS, 8MHz EuroDOCSIS
Receive Center
Frequency Range91 to 857MHz DOCSIS, 108 to 862MHz EuroDOCSIS
Input Level-15 to 15dBmV
Ordering Information
Model NumberDescription
XP-DSMDSM for XM2 Series Power Supplies
XP-DSM-VPDSM for XM2 VP Series Power Supplies
XP-DSM-EDEuroDOCSIS DSM for XM2 Series Power Supplies
XP-DSM-ED-VPEuroDOCSIS DSM for XM2 VP Series Power Supplies
XP-ESMESM for XM2 Series Power Supplies
XP-ESM-VPESM for XM2 VP Series Power Supplies
GMX-DSMDSM for GMX Series Power Supplies
GMX-DSM-EDEuroDOCSIS DSM for GMX Series Power Supplies
GMX-ESMESM for GMX Series Power Supplies
DSM-CRAFTDSM and ESM to Laptop Serial Interface Cable
XP-BSC-3-6Wire Kit, Battery Sense, 1x36V, 6’
XP-BSC-6-6Wire Kit, Battery Sense, 2x36V, 6’
XP-BSC-4-6Wire Kit, Battery Sense, 1x48V, 6’
Document Downloads
Title Type Version Date
AlphaNet ESM and DSM Datasheet - English Datasheet 049-233-12-008 June 1, 2008
AlphaNet XP-DSM Technical Manual Manual June 18, 2007
XP-DSM Hardware Installation Quick Start Guide Manual 745-814-B2-002 December 1, 2007
XP-DSM Network Configuration Quick Start Guide Manual 745-814-B1-002 December 1, 2007
XP-DSM Technical Support Manual August 18, 2008