General Specifications
| Output Rating: |
3.5kW |
5.0kW |
7.5kW |
| DC Output Voltage: |
39.0V ±0.5V @ no load 36V configuration
52.0V ±0.5V @ no load 48V configuration |
39.0V ±0.5V @ no load 36V configuration
52.0V ±0.5V @ no load 48V configuration |
52.0V ±0.5V @ no load 48V configuration
104.0V ±0.5V @ no load 96V configuration |
| DC Output Load Regulation: |
0.5V |
0.5V |
0.5V |
| Output Current: |
39.0V @ 90A max. / 52.0V @ 67A max. |
39.0V @ 128A max. / 52.0V @ 96A max. |
52.0V @ 144A max. / 104V @ 72A max. |
| Engine: |
398CC, Air cooled, Single OHV 10.5hp (using natural gas fuel) |
| RPM (Variable Speed): |
2800 to 3600RPM |
2800 to 3600RPM |
2800 to 3600RPM |
| Acoustical Noise |
| dBA 10’ @ 100% Rated Load: |
68.7 |
68.5 |
70.3 |
| dBA 20’ @ 100% Rated Load: |
63 |
62.5 |
64.3 |
| dBA 10’ @ 70% Rated Load: |
68.3 |
66.9 |
66.4 |
| dBA 20’ @ 70% Rated Load: |
62.6 |
60.9 |
60.4 |
| Models |
CE-3x2 |
CE-9x2 |
CE-3x2 |
CE-9x2 |
PN-6x |
| Dimensions H x W x D (in/mm): |
44 x 26 x 24 / 1117.6 x 660.4 x 609.6 |
52 x 26 x 24 / 1320.8 x 660.4 x 609.6 |
44 x 26 x 24 / 1117.6 x 660.4 x 609.6 |
52 x 26 x 24 / 1320.8 x 660.4 x 609.6 |
39 x 39.3 x 24 / 914 x 998.2 x 609.6
(57 x 39.3 x 24 / 1447.8 x 998.2 x 609.6 with optional pedestal) |
| Weight (lb/kg): |
383/174 |
413/187 |
383/174 |
413/187 |
338/174 (370/168 with optional pedestal) |
| APU Fuel Consumption |
| Natural Gas: 1000BTU/Ft.3: |
60ft3/hr |
80ft3/hr |
150ft3/hr |
| Propane Gas: 2520BTU/Ft.3: |
0.82gal/hr - 30ft3/hr - 3.46lb/hr |
1.10gal/hr - 40ft3/hr - 4.62lb/hr |
1.48gal/hr - 50ft3/hr - 6.24lb/hr |
| Exterior Surface Temperature: |
65˚C / 149˚F max)(meets requirements of UL/CSA) |
All Models
| Gas Inlet Pressure: |
0.5 to 2 PSI Inlet Pressure (Contact Alpha Engineering for additional supply resources) |
| Ign Charger Voltage: |
13.5Vdc |
| Ign Charger Current: |
6A max. |
| Remote Interface Length: |
75ft typical. Distance depends upon installation, de-rating and wire gauge. |
| Agency Compliance: |
UL1778, UL2200, NFPA 37/54/58 and 70, CSA C22.2 No.107.1, EMC/FCC Part 15 Class A |
| Fuel System, Controls and Monitoring: |
The controls and fuel system meet applicable sections of NFPA 37, 54 and 58 for automatic unattended operation of remotely located generators. Full System Control and Status Monitoring included. |
| Sensors: |
Gas hazard, pad shear, water intrusion and tamper |
| Safety Shutdowns: |
Low oil pressure, over temp, low fuel pressure shutdown (propane only), water intrusion, pad shear, gas hazard (propane or natural gas), over-speed, over-crank |
| Optional Feature: |
Cold Start Kit: provides additional starting capability at temperatures below -18°C / 0°F |