Select Your Country
ACS HP
ACS HP Series
  • Complete communication, system monitoring and control package
  • Reduced operating costs: unity power factor with efficiency > 93%
  • Wide input range: 187-312Vac single phase; 208-480Vac 3 phase
  • High power density with a small overall footprint
  • Limited spare parts requirement
  • Expandable to 175A output capacity; power options to 800A available
  • N+1/N+N redundancy capability; hot swappable design
  • Battery management and data logging are standard system features


The Alpha Charging System High Performance Series provides excellent reliability and ultimate efficiency in meeting the power requirements for many types of system applications. The ACS HP Series is designed to charge all types of stationary batteries (flooded lead acid, VRLA, and NiCd) for industrial, utility, petrochemical and fire/utility applications. A compact 4RU shelf accommodates up to five, hot swappable, fan cooled Cordex™ 4.4kW rectifiers. The 4.4kW Cordex rectifiers possess extremely high density, providing the most power in the least amount of space. Whether used in a local or remote setup, system adjustment and control is a simple single-step process via the Cordex CXC touch screen system controller or via an ethernet connection and an Internet browser. Battery management and data logging are standard system features.
ACS HP Series Modular Switched Mode Charger
Electrical
Input
Nominal Voltage208 to 240Vac
Operating Voltage187 to 312Vac
Extended Voltage187 to 90Vac (derated)
Phase1 or 3
Frequency45 to 70Hz
Current23A/module-nom. (130A Max@ 175ADC output)
Power4400W continuous/module
Power Factor>0.99 (50 to 100% load)
THD<5%
EfficiencyGreater than 93%
Output
Voltage90 to 160Vdc
Current35A/module-nom. (200A Max @ 110VDC)
Load RegulationStatic <±0.5%
Line RegulationStatic <±0.1%
Transient Response<±5% for 40 to 90% load step, 30ms recovery time
Ripple±30mVms Battery Eliminator
Mechanical
DimensionsStandardXL
mm1049 H x 622 W x 597 D1806 H x 700 W x 622 D
in41.5 H x 24.5 W x 23.5 D71.1 H x 27.55 W x 24.5 D
Weight100 kg (220 lb) for 105A System115 kg (253 lbs) for 105A System
CabinetNEMA 1 (black finish)NEMA 1 (black finish)
Environmental
Standard Temp-40˚ to 50°C (-40˚ to 122°F)
Extended Temp-40˚ to 75°C (-40˚ to 167°F)
Storage Temp-40˚ to 85°C (-40˚ to 185°F)
Humidity0 to 95% RH non-condensing
Elevation-500 to 2,800m (-1,640 to 9,186ft); to 4,000m (13,124ft) derated to 40˚C (104˚F)
Audible Noise350,000 hours
Standard Features
Full graphic touch screen LCD with virtual alphanumeric and numeric keyboards
Modbus Protocol
Access GUI user interface via Internet browser through Ethernet port or RS-232 craft port on CXC Controller
High interrupting current input and output breakers (10kA IC)
Reverse polarity protection
AC and DC surge suppression
Current limit protection
Soft start protection
Common Form C alarm relay contacts
High voltage shutdown
AC failure alarm
High/Low voltage alarm
Charger failure alarm
Positive/Negative ground fault alarm
DC output failure alarm
BAttery Temperature Compensation Probe (12ft); optional lengths available for purchase
Control Functions
FunctionsAutomatic, scheduled, or manual float charging (adjustable)
Automatic, scheduled, or manual equalize charging (adjustable)
High/Low voltage alarm setting (adjustable)
Charge current limit (adjustable)
Automatic or manual battery testing
Battery capacity and runtime prediction
Temperature compensation
Daily StatisticsMinimum, maximum and average on input channels, with date and time stamp. Battery current, rectifier current, and AC mains voltage for prior 90 days
Event LogOn all events such as alarms, power on, any change of state of the digital inputs, or other miscellaneous events
Battery LogBattery health history on last 20 discharges, time of discharge, and battery capacity
Options
Low voltage disconnect
DC Output Panel
Up to 10 x 2 Pole, 5-60A breakers (10kA IC) with alarm monitoring
DNP3 Level 2
Standards and Certifications
SafetyEN 60950
UL 60950-1 (pending)
CSAC22.2No. 60950-1-03
CE EN 60950, CB Scheme
Telcordia (Bellcore) GR-1089-CORE
EMCEN 55022 (CISPR 22)
EN 61000-3-2 EN 61000-3-3
EN 61000-4-2 EN 61000-4-3
EN 61000-4-4 EN 61000-4-5
EN 61000-4-6 EN 61000-4-11
ETS 300 019-1-1 ETS 300 019-1-2
ETS 300 753 IEC60950
ICES-003 Class B FCC Part 15 Class B
FCC Part 68
Document Downloads
Title Type Version Date
ACS HP Series Battery Quick Start Guide Manual AIP900-0012-B0-001 Rev. A January 1, 2012
ACS HP Series Modular Switched Mode Battery Chargers Datasheet 04935810002_09 February 3, 2012