Select Your Country
XM2 Series
  • Proven CableUPS® uninterruptible power
  • LCD Smart Display provides operating data, status information and troubleshooting aid
  • Modular design allows hotswappable inverter replacement
  • User programmable system control and status monitoring options
  • Easily accessible front panel connections
  • Programmable, three stage 10A, temperaturecompensated battery charger
  • Optional embedded transponder reduces external wiring for easier installation and improved reliablity
  • Optional embedded DOCSIS™ status monitoring
Alpha’s XM2 Series power supply is the industry’s leading power technology. A variety of power ratings make it an ideal match for network architectures worldwide. Advanced product design features include hot swappable modularity, and and intelligent diagnotic display. Optional independent dual outputs and N+1 redundant capability provide additional protection and enhanced system reliability. AC or DC generator compatibility, flexible system control and advanced status monitoring options support easy migration to clustered or centralized powering.
General Specifications
Input
Power Factor>0.90 at full load
Voltage±15%
Voltage (XM2-915/922 HV)-25 to +15%
Voltage (XM2-906G6/906G5)-30 to +20%
Frequency±3%
Output
WaveformQuasi-square wave
Regulation±5%
Frequency Stability±0.05% inverter mode, ±1% normal mode
Short Circuit Current150% of maximum current rating
Transformer Efficiency90% typical line mode
80% typical standby mode
Transfer CharacteristicsUninterrupted output
Battery Charger
Temperature CompensationProgrammable (0 to 5mV/Cell/°C)
Charger Current10A at 80% load and nominal input (bulk charge mode)
Charge Time8 hrs typical to 90% capacity
Three StageBulk, accept, float
Mechanical
Status Display2 x 20 LCD with backlight
Dimensions (in/mm)15 x 8.75 x 13 / 381 x 222 x 330
FinishBlack, epoxy powdercoat
Environment
Operating Ambient Temp.-40° to 55°C / -40° to 133°F
Relative Humidity0 to 95% non-condensing
Agency Compliance
FCC Part 15 Class A, UL1778, CSA 22.2 No. 107.1-M95
Smart Display Features
• Output Current• Built-in Diagnostics
• Input Frequency• Output Power (W)
• Battery Voltage• Output Voltage
• Battery Temperature•% load
• Output VA• Input Voltage
• Standby Time• Charger Current
Document Downloads
Title Type Version Date
XM2 Data Sheet - English (LTR) Datasheet 049-019-10-007 October 1, 2007
XM2 Data Sheet - English (A4) Datasheet 049-019-11-007 October 1, 2007
XM2 Data Sheet - Chinese (A4) Datasheet 049-019-27-004 April 1, 2006
XM2 Data Sheet - Czech (A4) Datasheet 049-019-29-001 August 1, 2005
XM2 Data Sheet - Russian (A4) Datasheet 049-019-28-003 June 1, 2004
XM2 Data Sheet - Japanese (A4) Datasheet 049-019-25-002 May 1, 2005
XM2 Data Sheet - Spanish (A4) Datasheet 049-019-30-002 March 1, 2006
Addendum to USM2.5 Status Monitor Technical Manual_Eng (LTR) Manual 018-041-C0-002 Rev. B July 1, 2002
XM Series 2 Power Supply Technical Manual Manual 017-805-B0-007 August 1, 2006
XM2 CableUPS Preliminary Inspection Manual 017-805-B5-006 August 1, 2006
XM2 SSC Operation and Maintenance Manual Manual 018-332-C0-002 Rev. B June 1, 2006
XM2 Technical Manual (Espanol) Manual 017-805-B6-001 Rev. A June 1, 2006
XM2 USM2 Operators and Technical Manual Manual 704-587-B0-003 Rev. D June 1, 2006
XM2 UPS Inverter Module Removal Installation (Video) Brochure June 1, 2006
XM2 UPS Optional PIM Installation (Video) Brochure June 1, 2006
XM2 UPS Output Voltage Change (Video) Brochure June 1, 2006
XM2 UPS Optional USM2 Installation (Video) Brochure June 1, 2006
XM2 UPS Setup and Test (Video) Brochure June 1, 2006
XM2 UPS Smart Display Use (Video) Video June 1, 2006
XM2 UPS Transformer Module Verification (Video) Video June 1, 2006